Alfaidro NOFIRE Multilayer Pipe (FASER SDR 7.4) is the alternative to metal systems in the fire protection sector. The PP-RCT pipe with a special flame retardant additive has a glass fibre middle layer that gives the pipes greater dimensional stability. In fact, one of the main advantages of NOFIRE pipes is the reduction in linear thermal expansion, which translates into a reduced amount of bracketing (-30%) and therefore reduced installation time and costs in wet sprinkler systems.
FASER SDR 7.4 multilayer pipe is self-extinguishing and particularly suitable for fire protection systems and can be assembled with the entire range fittings of Alfaidro NOFIRE, using traditional polyfusion techniques of pocket welding and electro-welding: the fumes produced are non-toxic and are therefore not harmful to people and animals.
GENERAL CATALOGS AND TECHNICAL DATA SHEETS IN
VARIANT Outside diameter Internal diameter Nominal thickness DN Water content (l/m) Weight (Kg/m) Rod size Pack size
NFTA200 20 mm 14,4 mm 2,8 mm 15 0,163 0,151 4 mt 120 mt
NFTA250 25 mm 18 mm 3,5 mm 20 0,254 0,236 4 mt 80 mt
NFTA320 32 mm 23,2 mm 4,4 mm 25 0,423 0,379 4 mt 48 mt
NFTA400 40 mm 29 mm 5,5 mm 32 0,660 0,589 4 mt 32 mt
NFTA500 50 mm 36,2 mm 6,9 mm 40 1,029 0,917 4 mt 24 mt
NFTA630 63 mm 45,8 mm 8,6 mm 50 1,647 1,442 4 mt 12 mt
NFTA750 75 mm 54,4 mm 10,3 mm - 2,323 2,052 4 mt 12 mt
NFTA900 90 mm 65,4 mm 12,3 mm 65 3,358 2,939 4 mt 8 mt
NFTA110 110 mm 79,8 mm 15,1 mm 80 4,999 4,401 4 mt 8 mt
NFTA1125 125 mm 90,8 mm 17,1 mm - 6,472 5,662 4 mt 4 mt
NFTA1160 160 mm 116,2 mm 21,9 mm 125 10,599 9,255 4 mt 4 mt
TEMPERATURES AND OPERATING PRESSURE:
SDR 11
20°C – 15.4 bar
60°C – 7.7 bar
70°C – 5.1 bar
SDR 9
20°C – 19.5 bar
60°C – 9.7 bar
70°C – 6.4 bar
SDR 6
20°C – 30.9 bar
60°C – 15.5 bar
70°C – 10.2 bar
SDR 5
20°C – 39.8 bar
60°C – 19.5 bar
70°C – 12.8 bar
WORKING TEMPERATURES:
MIN= -20°C MAX= +95°C
REGULATION FOR DRINKING WATER:
DM 174-06/04/2004 (Italy), DM 23/04/2009 e Reg. UE n° 10/2011
REFERENCE STANDARDS:
- Sistema antincendio [Firefighting system]: NFPA 13, 13R, 13B, FM 1635, UL 1821, UNI EN 12845, UNI EN 13501-1, UNI EN 671, DIN 4102-1
- Sistema [System]: UNI EN ISO 15874, ISO 15495, DIN 8077, DIN 8078, DIN 16962, ASTM F2389, BS 4991, CSA B137.11
- Prove [Tests]: UNI EN ISO 15874, DIN 16962, ISO 1133, ISO 3126, ISO 1167, ISO 2501, ISO 9854, UL 1821, FM 1635
NOFIRE LINE CERTIFICATES:
- FM APPROVALS : USA
- WARRINGTONFIRE : AbP – Germany
- APCI : Cuba